OSHA Fire Extinguisher Mounting Height, Placement & Signage Requirements

Fire Extinguisher Safety Image
In some cases, OSHA requires employers to have fire extinguishers at work, and in other cases, employers will choose to provide fire extinguishers. In either scenario, if a company will place portable fire extinguishers in the workplace, it’s important to know OSHA requirements covering mounting fire extinguishers and fire extinguisher placement as well as as OSHA fire extinguisher signage requirements.

We’ll cover each of those three issues–fire extinguisher mounting height, fire extinguisher placement, and fire extinguisher signage requirements–in this article.

OSHA Fire Extinguisher Mounting Height, Placement & Signage Requirements

Let’s look at the OSHA requirements for each of these issues.

OSHA Fire Extinguisher Placement

The issue of fire extinguisher placement requirements from OSHA begins with cases in which OSHA requires the employer to have portable fire extinguishers and/or the employer decides to.

If portable fire extinguishers will be present, 1910.157(c)(1) lays down the first requirement:

The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury.

So the key issue above is “readily accessible to employees without subjecting the employees to possible injury.” Please note this is assuming the employer allows employees to use the extinguishers.

Fire Extinguisher Placement Image

The next concern about fire extinguisher placement is the distance the employee has to travel to reach an extinguisher. This is based on the type of extinguisher (and/or the Class of fire it can put out), as listed below.

Placement of portable fire extinguishers for Class A fires

Portable fire extinguishers must be placed so that the travel distance for employees to any extinguisher is 75 feet or less. — see 1910157(d)(2)

In addition, here’s what an OSHA Evacuation Plans and Procedures eTool (on the Extinguisher Placement and Spacing page) says regarding extinguishers for Class A fires:

The National Fire Protection Association (NFPA) recommends that locations such as offices, classrooms, and assembly halls that contain mainly Class A combustible materials have one 2-A extinguisher for every 3,000 square feet. [Standard for Portable Fire Extinguishers (NFPA 10 (2010), Table 6.2.1.1, Fire Extinguisher Size and Placement for Class A Hazards)].

OSHA requires that all employees have access to an extinguisher within 75 feet travel-distance. [29 CFR 1910.157(d)(2)]

NOTE: Uniformly spaced standpipe systems or hose stations connected to a sprinkler system for emergency use can be used instead of Class A portable fire extinguishers, if they meet the respective requirements of 29 CFR 1910.158 or 29 CFR 1910.159, provide total coverage of the area to be protected, and employees are trained at least annually in their use. [29 CFR 1910.157(d)(3)]


Placement of portable fire extinguishers for Class B fires

Portable fire extinguishers must be placed so that the travel distance for employees to any extinguisher is 50 feet or less.– see 1910.157(d)(4)

In addition, here’s what an OSHA Evacuation Plans and Procedures eTool (on the Extinguisher Placement and Spacing page) says regarding extinguishers for Class B fires:

Hazard Extinguisher Spacing
Light (Low)

Small amounts of flammable liquids used for copy machines, art departments, etc., that are stored safely and kept in closed containers.

5-B 30 feet
Light (Low)

Small amounts of flammable liquids used for copy machines, art departments, etc., that are stored safely and kept in closed containers.

10-B 50 feet
Ordinary (Moderate)

The total amount of flammable liquids are present in greater amounts than expected under low-hazard locations. This can include garages, workshops, or support service areas.

10-B 30 feet
Ordinary (Moderate)

The total amount of flammable liquids are present in greater amounts than expected under low-hazard locations. This can include garages, workshops, or support service areas.

20-B 50 feet
Extra (High)

Locations where flammable liquids are present and used in large quantities. This includes areas used for storage, production, woodworking (finishing), vehicle repair, aircraft and boat servicing, or where painting, dipping, and coating, operations are performed with flammable liquids.

40-B 30 feet
Extra (High)

Locations where flammable liquids are present and used in large quantities. This includes areas used for storage, production, woodworking (finishing), vehicle repair, aircraft and boat servicing, or where painting, dipping, and coating, operations are performed with flammable liquids.

80-B 50 feet

OSHA notes they’ve adapted this information above from “Standard for Portable Fire Extinguishers,” NFPA 10 (2010), Table 6.3.1.1, Fire Extinguisher Size and Placement for Class B Hazards

Placement of portable fire extinguishers Class C fires

Here, OSHA says “The employer shall distribute portable fire extinguishers used for Class C hazards on the basis of the appropriate pattern for the existing Class A or Class B hazards.”– see 1910.157(d)(5)


Placement of portable fire extinguishers for Class D fires

OSHA has a little more to say for Class D fires. Here’s what they say: “The employer shall distribute portable fire extinguishers or other containers of Class D extinguishing agent for use by employees so that the travel distance from the combustible metal working area to any extinguishing agent is 75 feet (22.9 m) or less. Portable fire extinguishers for Class D hazards are required in those combustible metal working areas where combustible metal powders, flakes, shavings, or similarly sized products are generated at least once every two weeks.”– see 1910.157(d)(6)

Placement of portable fire extinguishers for Class K fires

The placement of extinguishers for Class K fires isn’t directly covered the 1910 OSHA regulation, but is addressed in an OSHA Evacuation Plans and Procedures eTool (on the Extinguisher Placement and Spacing page). Here’s what that eTool says:

Locations where potential fire hazards from combustible cooking media (vegetable or animal oils and fats) exist must install Class K extinguishers at a maximum travel distance of 30 feet. [NFPA 10, Standard for Portable Fire Extinguishers. See Section 6.6, Installations for Class K Hazards]

Americans with Disabilities Act & Fire Extinguisher Placement Issues

Although we’re focusing on OSHA regulations concerning fire extinguishers, remember that you may also have to consider things like local building codes, NFPA requirements (check NFPA 10), and even the Americans with Disabilities Act (ADA).

According to the ADA, if an object is mounted to the wall (like fire extinguishers often are), and their leading edges are located between 27 inches and 80 inches above the finished floor, the mounted object can protrude no more than four inches into walkways, corridors, passageways, or aisles. This is at least one reason why you’ll often see fire extinguishers inside recessed cabinets within a wall instead of mounted on the wall and sticking out into a traffic way.


OSHA Fire Extinguisher Mounting Height Requirements

Now let’s turn our attention to fire extinguisher mounting height requirements.

If you go back to 1910.157(c)(1), you’ll see all the OSHA regulation has to say on the issue of mounting height:

The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury.

So the key in there is to make sure “they are readily accessible to employees without subjecting the employees to possible injury.”

BUT, OSHA has an Evacuation Plans and Procedures eTool with a page dedicated to fire extinguisher mounting and placing, and that page says:

To prevent fire extinguishers from being moved or damaged, they should be mounted on brackets or in wall cabinets with the carrying handle placed 3-1/2 to 5 feet above the floor. Larger fire extinguishers need to be mounted at lower heights with the carrying handle about 3 feet from the floor.

Fire Extinguisher Mounting Image

OSHA Fire Extinguisher Signage Requirements

And finally, let’s turn our attention to OSHA’s fire extinguisher signage requirements.

As we did before, let’s go back to 1910.157(c)(1). Here’s what OSHA says about signage requirements for fire extinguishers:

The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury.

Notice there’s nothing specific about signage. All the 1910 regulation says is the portable fire extinguishes should be “identified.”

So here, you’re best off following good-old common sense. Place a sign or something similar that makes it easy for people to know where an extinguisher is/extinguishes are. Consider placing it so it can be seen well from up close, at a distance, and from different angles. And make sure there’s nothing that obstructs a person’s view of the extinguisher and/or the sign (such as a pile of boxes, machinery, or an open door).

Fire Extinguisher Signage Image

Additional Articles About Fire Extinguishers That May Interest You

In addition to this article, you may find the following articles related to fire safety and fire extinguishers helpful:

Finally, you may want to consider our online fire extinguisher safety training video. We’ve included a short sample of it immediately below.

The Wrap Up: OSHA Fire Extinguisher Mounting Height, Placement & Signage Requirements

We hope this answered some of your questions about fire extinguisher placement, signage, and mounting requirements. Please remember that fires are a real hazard, that every year people die from fires unnecessarily, and that with proper precaution and safety training we can all make sure a lot more people make it home from work alive and well.

Before you leave, please download our FREE ONLINE SAFETY TRAINING BUYER’S GUIDE CHECKLIST, BELOW.

Online Safety Training Buyer's Guide Checklist

Online Safety Training Buyer’s Guide Checklist

Learn how to evaluate the different online safety training solutions that exist to find one that best fits your company’s needs with our FREE informative guide and checklist.

Download Free Guide

Online Safety Training Buyer's Guide Checklist
Jeffrey Dalto

Jeffrey Dalto

Jeffrey Dalto is an Instructional Designer and the Senior Learning & Development Specialist at Convergence Training. He's worked in training/learning & development for 25 years, in safety and safety training for more than 10, is an OSHA Authorized Outreach Trainer for General Industry OSHA 10 and 30, has completed a General Industry Safety and Health Specialist Certificate from the University of Washington/Pacific Northwest OSHA Education Center and an Instructional Design certification from the Association of Talent Development (ATD), and is a member of the committee creating the upcoming ANSI/ASSP Z490.2 national standard on online environmental, health, and safety training. Jeff frequently writes for magazines related to safety, safety training, and training and frequently speaks at conferences on the same issues, including the Washington Governor's Safety and Health Conference, the Oregon Governor's Occupational Safety and Health Conference, the Wisconsin Safety Conference, the MSHA Training Resources Applied to Mining (TRAM) Conference, and others.

20 thoughts on “OSHA Fire Extinguisher Mounting Height, Placement & Signage Requirements

      1. I need some basic info. But, don’t think I need whole books. Is there a place to just ask a couple questions?

  1. Is there any guildance on how to handle a fire extinguisher after it has been removed from its storage location? My concern is with tripping over the extinguisher and damage to the cylinder causing it to become a missle.

  2. Is there anything that says how much free space there should be around a fire extinguisher? I had heard a 3′ square, but cannot seem to find this in writing.

  3. Jeffrey, In a rental home, what are the actual sign size and color requirements informing guests of location of fire extinguishers. Is the copy “Fire Extinguishers Located Inside” approved copy? Thank you, debby

  4. I was told during a government safety inspection in Northern Nevada that a fire extinguisher has to be a certain distance from and an exit door. Please tell what that distance is. Thank you

    1. Erick,

      A good question and I’ll start by saying I don’t know the exact answer.

      The easy way to answer this is with an answer you probably already know. In a fire, we want nothing to interfere with the ability to access and use a fire extinguisher, so you should keep things well away from the extinguisher.

      That said, you’re probably looking for something exact, measured in feet/inches or meters/centimeters. I’d recommend contacting your local OSHA office and/or consulting the NFPA 10 Standard for Portable Fire Extinguishers: https://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes-and-standards/detail?code=10

      Good luck!

        1. You bet. Sorry the best I could do was point you to where I think you can find the answer. But I do think one of those two can tell you something more accurate than I can. Good luck!

  5. Please remember that OSHA is a minimum standard. To be fully informed you should also review the International Fire Code and the Life Safety Code that has been adopted by your local jurisdiction. Talk to your local fire inspector and or your insurance company as to what they require.